  1. Life Safety Recall

    Honeywell Recalls Gamewell-FCI and Notifier Photoelectric Smoke Sensors Sold with Fire Alarm Systems Due to Failure to Alert of a Fire!
    IV Series photoelectric detectors operating in CLIP within the affected date range must be immediately removed from service and replaced. Any inventory must be returned for credit. This Safety Bulletin should be communicated to the site coordinator of all potentially impacted installations.

    This recall involves “-IV” Intelligent photoelectric smoke sensors sold with fire alarm systems installed primarily in commercial buildings; not sold to retailers or consumers. The smoke sensors are round, ivory in color, and measure four inches in diameter. The model number, date codes and Honeywell or Notifier are printed on the back label of the smoke sensor. The smoke sensors have the following brand names, model numbers, date codes, and configuration. 

    Gamewell-FCI
    ASD-PL3-IV,
    ASD-PL3R-IV, and ASD-PTL3-IV
    With date codes
    8034 to 9013
    Notifier
    FSP-951-IV, 
    FSP-951R-IV,
    FSP-951T-IV
    No date code provided

    NOTIFIER recalls FSP-951-IV Series Photoelectric Detectors Operating in CLIP Protocol

    Recall Summary:

    Name of Product: FSP-951-IV Series Photoelectric Detectors Operating in CLIP Protocol

    Date Range: March 30, 2018 – January 14, 2019

    Date Code Range: 8034 through 9013

    Hazard: When these models are used in conjunction with the NOTIFIER ONYX NFS-3030 and NFS2-3030 Fire Alarm Control Panels (FACP) operating in CLIP they have the potential to not properly communicate a fire alarm condition in certain fire scenarios such as a fast, flaming fire.

    Remedy Replacement: FSP-951-IV Series photoelectric detectors operating in CLIP within the affected date range must be immediately removed from service and replaced. Any inventory must be returned for credit. 

    Consumer Support: Technical questions should be directed to NOTIFIER Technical Support at 1-800-289-3473 or NOTIFIER.Tech@honeywell.com

    https://cpsc.gov/Recalls/2019/Honeywell-Recalls-Gamewell-FCI-and-Notifier-Photoelectric-Smoke-Sensors-Sold-with-Fire-Alarm-Systems-Due-to-Failure-to-Alert-of-a-Fire

    Like

Leave a Reply

Fill in your details below or click an icon to log in:

WordPress.com Logo

You are commenting using your WordPress.com account. Log Out /  Change )

Google photo

You are commenting using your Google account. Log Out /  Change )

Twitter picture

You are commenting using your Twitter account. Log Out /  Change )

Facebook photo

You are commenting using your Facebook account. Log Out /  Change )

Connecting to %s

This site uses Akismet to reduce spam. Learn how your comment data is processed.